Typical Installations
|
- Automatic fool-proof zeroing
- Threaded instrument and process connections
- Gives full transmitter serviceability
- Straight-thru 1/4" roddable ports
- Unique bonnetless tapered plug design
- Adjustable packing nut stops interport and stem leakage
- No metal to metal contact
- Barstock construction
- Bubble tight seals
- Directional arrowhead handle with positive stops
- All parts replaceable in-line
- Mounting holes and U-bolts furnished for 2" pipe mounting
|
The D/A MINIMATIC series of "3-valve"
manifolds perform all the necessary functions of a 3-valve system by
utilizing two 3-way valves working together instead of three
independent 2-way valves. This sensible concept allows the operator to
simply dial NORMAL, ZERO or BLOCKED with a 90 degree turn of the handle
rather than manipulating a cluster of independent valves. Because the
unique design of the MINIMATIC properly groups and
interlocks the porting to provide automatic, fool-proof
sequencing, it can drastically reduce the costly
errors of improper operation inherent in 3-valve systems
resulting in steam damaged transmitters, plugged tap lines and flushed
out winterizing.
The D/A MINIMATIC - Adding an Extra Dimension of Simplicity,
Convenience and Safety to Instrument Manifolding.
|
Operation
|
Service Mode
Zeroing Mode
Isolation Mode
Note: Because of the unique fool-proof design,
the Zeroing Valve and Blocking Valve handles can be dialed to their
respective positions in any order without causing improper operation.
|
Service Mode
With both valve handles in the normal position, the MM6AT is in the
service mode with both process inlets open and the equalizing
port blocked.
Zeroing Mode
By dialing the Zeroing Valve handle to the ZERO position, the MM6AT is
automatically switched to the zeroing mode which completely and
properly prepares the transmitter for zeroing by (1)first blocking one
inlet impulse line and (2) then opening the equalizing port which
bypasses the blocked inlet to equalize the P cell at process
pressure. Because it basically operates like a 3-way valve, this forced
zeroing sequence provides fool-proof operation and safety. After
correcting for zero offset, the transmitter is returned to service by
simply redialing the handle to the NORMAL position which, again,
correctly sequences back to the service mode by closing the equalizer
first and then reopening the blocked inlet.
Isolation Mode
By dialing the Zeroing Valve and Blocking Valve handles to the ZERO and
BLOCKED positions respectively, the MM6AT is automatically switched to
the islolation mode where both inlets are blocked and the
equalizing port is closed. The transmitter is now safely isolated and
prepared for field servicing, recalibration or removal. The transmitter
is returned to service by simply redialing the handles to their NORMAL
positions which, again, correctly sequences back to the service mode by
leaving the equalizer blocked and reopening both inlets.
|
Specifications
|
Max Ratings:
Teflon:
6000psi @ -150ºF to 150ºF
2500psi @ 220ºF
Ryton:
6000psi @ 300ºF
2500psi @ 520ºF
Connections:
1/2" FNPT instrument x 1/2" FNPT process
Design Codes:
ANSI B31.1, B16.5, NACE MR-01-75(special
order)
Material Codes:
Barstock, A479 - 316, A276-316;
Cast, ASTM-A743 CF3M, ASTM-A-351 CF3M, A 276-316.
|
Materials of Construction:
Body: 316SS or nickel plated C.S.
Wetted Plug: 316SS
Plug Liner: Teflon or Ryton reinforced Teflon
Non-Wetted Trim: 303SS
Handle: Cast aluminum arrowhead - PVC coated
Nameplate: SS embossed
Exotic materials: Hastelloy C, Monel, Alloy 20,
etc. consult factory.
|